Type | Gutor SDC Rectifier / Battery Charger | |
Ratings | 24-220 V(Higher ratings upon request) | 25-1200 A(Higher ratings upon request) |
Operating temperature | – 10 to +40 °C (max. 55 °C on request) | |
Allowable air humidity | < 95 % (non condensing) | |
Noise level | 55 – 65 dBA (depending on rating) | |
Communication protocols | Modbus RTU, Webpage (HTTP), Modbus TCP, IEC 61850 (others on request) | |
Input | ||
Rectifier | 6-pulse thyristor bridge (12-pulse on request) | |
Voltage | 3 x 380 / 400 / 415V (other voltages on request) | |
Voltage tolerance | +/- 2% | |
Output | ||
Voltage | 24 / 48 / 110 / 125 / 220 VDC | |
Tolerance (static) | +/- 2 % | |
Frequency stability (free running) | < 0.01 % | |
Efficiency | up to 94% depending on type | |
DC overcurrent capability | 150 – 200% for 2s |
Oil & Gas
Nuclear
Power Gen
Other Industrial Segments
Features
Industrial thyristor rectifier from 25- 1200ADC and higher
With its broad range of possible DC voltages, the SDC is very flexible and can meet specific requirements and a wide range of autonomy times. Similar to the other products built on the xxW platform (PxW and WxW), the SDC will withstand the harshest environmental conditions. The firmware is certified according to IEC60880 for NPP (Nuclear Power Plant) applications.
This product is best in its class, because it benefits from our focus on quality and attention to detail.
Applications
– Nuclear Power Plants (NPP)
– Oil & Gas, Petrochemical (onshore, offshore, pipelines, refining, FPSO)
– Power generation, including transmission and distribution
– Chemical industry
– Other industrial applications
BENEFITS OF GUTOR SDC
Flexibility
Due to the fact of independent power modules, the rectifier and the inverter part of the UPS can be sized individually.
NPP qualified
The firmware is certified according to IEC 60880 for third party, and the components withstand applicable seismic requirements.
Proven reliability
Best in class Mean Time Between Failures (MTBF) within long product lifetime with minimal servicing required. Over 20,000 systems installed worldwide with excellent quality records.